Short-circuit calculation and selectivity: how to check a single-line diagram

Short answer: A short-circuit calculation finds the highest current a fault can produce and ensures that the breaking capacity (Icu) of every protective device is not lower than that current. Selectivity aims for only the protective device closest to the fault to trip.

Why is a short-circuit calculation done?

A short-circuit calculation finds the highest current that can occur at a board and in a cable during a fault. If a protective device has a breaking capacity (Icu) lower than this value, the device may not be able to interrupt the current safely. The calculation method is generally based on the IEC 60909 approach.

For a rough check, the short-circuit current at the transformer output is found with Ik ≈ In / uk, neglecting the network impedance. For example, for a 1000 kVA, 400 V transformer with 6% short-circuit voltage (uk), In is about 1443 A and Ik about 24 kA. This value is the starting point for the main board breaker; the detailed calculation also includes cable impedances and motor contributions.

Transformermax IkMain boardIcu checkDistributionselectivitySub-boardprotection settingLoadcable, circuit end
Diagram 1 — Single-line levels: breaking capacity, selectivity and cable protection are checked separately at each level.

What is selectivity and how is it achieved?

Selectivity means that during a fault only the protective device nearest to the faulted circuit trips while the upstream device stays closed, so a fault does not black out the whole installation. The main methods are:

  • Current selectivity: choosing different settings between levels.
  • Time selectivity: giving the upstream level a short delay.
  • Energy selectivity: selecting device combinations according to manufacturer tables.

If the downstream device has insufficient breaking capacity, the upstream device can back it up (cascading); however, full selectivity may be lost in that case.

What to check on a single-line diagram

CheckWhat to look atNote
Breaking capacityIcu must exceed the highest short-circuit current at that pointChecked at every board
Cable thermal withstandThe withstand of the cable during the fault (I²t)Cable size and clearing time are evaluated together
SelectivityManufacturer curves and selectivity tablesChecked between levels
End-of-circuit faultThe lowest fault current must trip the protectionCritical on long lines
Earthing systemProtection suited to a TN or TT systemTogether with residual current protection

Frequently asked questions

Click a question to see the answer.

AUIB Hospital, Bağdat
SelectivityCan full selectivity always be achieved?
Not always; it depends on device characteristics and cost. Full selectivity is targeted in critical facilities such as hospitals and data centers, while partial selectivity may be acceptable elsewhere.
Gaziosmanpaşa Adalet Sarayı
Calculation toolWhich software is used for the calculation?
Manufacturer software and tables are used for simple systems, and power system analysis software such as ETAP for complex networks.
Akfen İnşaat Merter Ofis Binası
RevitDoes Revit calculate short circuits?
No. Revit carries board and circuit data; short-circuit and selectivity calculations are done in specialist software and the results are fed back into the model.