How is cleanroom HVAC designed?

Short answer: Cleanroom HVAC is designed for the room's target ISO 14644-1 cleanliness class. The class sets the filtered air volume, the HEPA filter layout, the airflow pattern (unidirectional or mixed) and the pressure cascade between rooms. Temperature, humidity and pressure are monitored continuously, and the facility is documented with particle counts and validation tests at commissioning.

What is a cleanroom and where is it needed?

A cleanroom is a controlled space where airborne particles are kept below a defined limit. Pharmaceutical production, aseptic filling, semiconductor and electronics manufacturing, precision optics, biotech laboratories and some hospital units require cleanroom conditions.

ISO classes and design values

ISO 14644-1 defines cleanliness classes by the number of particles per cubic metre of air. The lower the class number, the cleaner the room and the faster the required air volume rises. The values below are common ranges for preliminary design; final values follow the process and risk assessment.

ClassTypical useAirflowPreliminary air changes
ISO 5Aseptic filling, critical zoneUnidirectional (laminar)Designed by air velocity, about 0.36–0.54 m/s
ISO 6Electronics assembly, support areasMixed / partial laminar90–180 per hour
ISO 7Pharmacy compounding, ISO 5 backgroundMixed flow30–60 per hour
ISO 8Packaging, gowning roomsMixed flow10–25 per hour

Pressure cascade: air must flow from clean to less clean

Cleanrooms are kept at higher pressure than adjacent areas so that air flows outward when a door opens. A difference of about 10–15 Pa between successive classes is typical. For toxic or biohazard processes the opposite applies: the room is kept negative to its surroundings and supported by airlocks.

ISO 5Highest pressureISO 7+10–15 PaISO 8+10–15 PaAirlockTransitionCorridorReference
Figure 1 — Pressure cascade from the clean zone to the corridor.

Filtration, temperature and humidity

  • Terminal filters are ceiling-mounted HEPA (H13–H14) filters, with coarse and fine filters upstream.
  • Temperature and relative humidity are held within tight tolerances for the process and staff comfort, increasing dehumidification and humidification capacity.
  • Low-level return grilles remove particles from near the floor.
  • The building management system continuously logs pressures, temperature, humidity and filter differential pressures.

Energy: the hidden cost of cleanrooms

High air change rates make cleanrooms energy-intensive. More recirculation, fan filter units, heat recovery and controlled flow setback outside operating hours significantly reduce operating cost. These decisions must be made early in design.

Commissioning and validation

A cleanroom is proven by testing, not by drawings. Commissioning includes HEPA leak tests, airflow and velocity measurements, pressure cascade checks, particle counts and recovery tests. In pharmaceutical facilities these tests are documented under GMP requirements.

See our Services page for details of Sönmez Mühendislik's services, and our Blog for more technical articles.

Frequently asked questions

Click a question to see the answer.

Haseki Hospital — 70,800 m²
BasicsHow is a cleanroom different from normal air conditioning?
Normal air conditioning provides comfort. A cleanroom system keeps particles, pressure, temperature and humidity within set limits and proves it by testing.
ClassWhich ISO class do I need?
The class is set by the process and applicable regulations: GMP grades for pharmaceuticals, product sensitivity for electronics.
PressureWhy does pressure difference matter?
It makes air flow out of the cleanroom when a door opens, keeping less clean air out.
Haseki Hospital — 70,800 m²
FiltersHow often are HEPA filters replaced?
Based on filter differential pressure monitoring and periodic leak tests, not a fixed interval.
EnergyHow can cleanroom energy use be reduced?
More recirculation, efficient fans, heat recovery and controlled flow reduction outside operating hours.
ExistingCan an existing space be converted into a cleanroom?
Usually yes. Storey height, plant room space and shaft options must be checked first.