Seismic bracing: how are pipes, ducts and cable trays protected in an earthquake?
The structure may stand, but the building may not work
Investigations after major earthquakes show that many buildings with undamaged structures could not be used because of damaged services. Broken sprinkler pipes cause flooding, fallen cable trays cut power and toppled equipment endangers lives. That is why non-structural elements must be designed for earthquakes as well.
Where is seismic bracing needed?
- Sprinkler and fire water systems (mains and distribution)
- Heating, cooling and domestic water pipes, especially large diameters
- Ductwork and air handling unit connections
- Cable trays, busbar trunking and heavy luminaires
- Suspended units and fans; floor-mounted switchboards, chillers, generators, UPS and battery racks
- Medical gas lines and other critical hospital systems
How does it work?
Normal hangers carry only vertical load. Seismic systems add braces (steel cable or rigid section) that restrain the services in the transverse and longitudinal directions. When the building moves, the services move with it in a controlled way instead of swinging freely.
| Component | Function | Key point |
|---|---|---|
| Transverse brace | Limits sideways sway | Spacing set by pipe size and seismic load |
| Longitudinal brace | Prevents sliding along the run | Extra braces at bends and changes of direction |
| Flexible connection | Accommodates movement at joints | Always used at building seismic joints |
| Anchor | Fixes the hanger to concrete or steel | Certified anchors suitable for cracked concrete |
| Equipment restraint | Stops heavy equipment toppling or sliding | Seismic snubbers needed on vibration-isolated equipment |
How is it designed?
Design follows the non-structural element provisions of the Turkish Building Earthquake Code (TBDY 2018); for sprinklers the seismic protection provisions of NFPA 13 are also widely used. Calculated loads must be checked with the structural design for the beams and slabs the anchors attach to.
Reserving space in the BIM model
Braces take much more space than normal hangers. If no space is reserved in the ceiling void, braces are either omitted on site or clash with other services. Seismic elements should therefore be shown in the Revit model and included in Navisworks clash detection.
See our Services page for details of Sönmez Mühendislik's services, and our Blog for more technical articles.
Frequently asked questions
Click a question to see the answer.
BasicsIs seismic bracing mandatory?

ScopeWhich services should be braced?
ExistingCan it be retrofitted in an existing building?
CostHow much does seismic bracing add to cost?

JointsWhat happens at seismic joints?
EquipmentHow is vibration-isolated equipment protected?
Let us protect your building services against earthquakes.
Since 1995, Sönmez Mühendislik has delivered structural, electrical, mechanical and BIM projects in Türkiye and abroad, and is one of Türkiye's long-established engineering offices. With more than 80 specialists we provide engineering design, technical consultancy and project management.