Hydronic balancing in heating and cooling systems: how to select a balancing valve
Why is hydronic balancing needed?
In heating and cooling systems, the pump pushes water toward the path of least resistance. Without balancing, risers close to the pump receive too much flow and distant ones too little. As a result, nearby rooms overheat or overcool, distant ones fail to reach comfort conditions, the pump is selected larger than needed and energy use and noise increase.
Kv value and valve selection
Valve capacity is defined by Kv: Q = Kv × √Δp (Q in m³/h, Δp in bar). For example, if 2 m³/h of flow needs a 0.3 bar pressure difference across the valve, Kv = 2 / √0.3 ≈ 3.65. The selected valve should operate in the middle of its setting range rather than fully open.
| Valve type | What it does | When to use it |
|---|---|---|
| Manual balancing valve | Provides an adjustable fixed resistance and a measuring connection | Riser bases, constant-flow circuits |
| Differential pressure controller | Keeps the pressure difference across a riser constant | Variable-flow risers |
| Pressure-independent balancing and control valve (PICV) | Limits flow and provides control | Fan coils, air handling units, terminal units |
Valve authority
For control valves, authority is the ratio of the pressure drop across the fully open valve to the total loss of the valve and circuit: a = Δp valve / (Δp valve + Δp circuit). If authority is too low, the valve cannot control flow effectively; a value above 0.3 is generally targeted.
Commissioning and documentation
- Calculated flows and preset values are written into the valve schedule.
- During commissioning, settings are adjusted with a measuring instrument (test, adjust and balance).
- Measured flows and pressure differences are reported.
- In variable-flow systems, verification is done together with pump speed control.
Frequently asked questions
Click a question to see the answer.
Terminal unitsDoes every fan coil need a balancing valve?

DesignHow are balancing valves shown in the project?

SymptomsHow can you tell a system is unbalanced?

Let us prepare your mechanical project with its calculations, coordinated with the other disciplines.
Since 1995, Sönmez Mühendislik has delivered structural, electrical, mechanical and BIM projects in Türkiye and abroad, and is one of Türkiye's long-established engineering offices.
See our Services page for more details.