Blog · Mechanical · 6 min read

Hydronic balancing in heating and cooling systems: how to select a balancing valve

Short answer: Hydronic balancing ensures that every riser and terminal unit receives the design flow. For this, balancing valves are selected according to the calculated flow, preset values are assigned and they are verified by measurement during commissioning.

Why is hydronic balancing needed?

In heating and cooling systems, the pump pushes water toward the path of least resistance. Without balancing, risers close to the pump receive too much flow and distant ones too little. As a result, nearby rooms overheat or overcool, distant ones fail to reach comfort conditions, the pump is selected larger than needed and energy use and noise increase.

Flow calculationzone loadsPipe networkpressure lossValve Kvpreset valueCommissioningmeasure, adjustReportflow, Δp records
Diagram 1 — Hydronic balancing flow: valve settings chosen by calculation are verified by on-site measurement and reported.

Kv value and valve selection

Valve capacity is defined by Kv: Q = Kv × √Δp (Q in m³/h, Δp in bar). For example, if 2 m³/h of flow needs a 0.3 bar pressure difference across the valve, Kv = 2 / √0.3 ≈ 3.65. The selected valve should operate in the middle of its setting range rather than fully open.

Valve typeWhat it doesWhen to use it
Manual balancing valveProvides an adjustable fixed resistance and a measuring connectionRiser bases, constant-flow circuits
Differential pressure controllerKeeps the pressure difference across a riser constantVariable-flow risers
Pressure-independent balancing and control valve (PICV)Limits flow and provides controlFan coils, air handling units, terminal units

Valve authority

For control valves, authority is the ratio of the pressure drop across the fully open valve to the total loss of the valve and circuit: a = Δp valve / (Δp valve + Δp circuit). If authority is too low, the valve cannot control flow effectively; a value above 0.3 is generally targeted.

Commissioning and documentation

  • Calculated flows and preset values are written into the valve schedule.
  • During commissioning, settings are adjusted with a measuring instrument (test, adjust and balance).
  • Measured flows and pressure differences are reported.
  • In variable-flow systems, verification is done together with pump speed control.

Frequently asked questions

Click a question to see the answer.

Harbiye Ordu Evi yenileme projesi
Terminal unitsDoes every fan coil need a balancing valve?
If pressure-independent valves are not used, balancing is required at riser and circuit level. With PICVs, a separate balancing valve at each terminal is often unnecessary.
Gaziosmanpaşa Adalet Sarayı
DesignHow are balancing valves shown in the project?
Valve locations are shown on schematics and plans; flow, Kv and preset values are given in the valve schedule.
AUIB Hospital, Bağdat
SymptomsHow can you tell a system is unbalanced?
Temperature differences between rooms on the same line, noise in nearby risers and the pump constantly running at high speed are the main signs.