Blog · Electrical · Low Current · 6 min read · Updated: · Sönmez Mühendislik Engineering Team

How is a structured cabling and data infrastructure design prepared?

Short answer: Structured cabling connects all data, voice, security and automation devices in a building with one standard, organised and scalable cabling infrastructure. The design covers the layout of the main and floor telecom rooms, backbone (fibre) and horizontal (copper) cabling, cable category selection, tray routes, labelling and testing.

Why “structured”?

When every system pulls its own cables, buildings end up with a messy, undocumented infrastructure that cannot grow. Structured cabling connects every endpoint with the same hierarchy and standards. Computers, IP phones, cameras, wireless access points, access control and building automation share the same infrastructure. The international references are the TIA-568 and ISO/IEC 11801 families of standards.

Layers of the infrastructure

EntranceCarrier linesMain roomCore switchesBackboneFibre distributionFloor roomFloor patch panelsEndpointOutlet, camera, AP
Figure 1 — Structured cabling hierarchy.
  • Main telecom room: houses the building's core network equipment and needs power, cooling and access control.
  • Backbone cabling: links the main room to floor rooms, usually with fibre and redundant routes.
  • Horizontal cabling: copper cables from the floor room to the endpoints. The permanent link is limited to 90 m and the full channel with patch cords to 100 m.

Choosing the cable

Cable typeTypical useNote
Cat6Standard office outletsFine for 1 Gbit/s; limited distance at 10 Gbit/s
Cat6ANew projects, wireless access points10 Gbit/s at 100 m; better heat performance with PoE
Multimode fibre (OM4)In-building backboneHigh speed over short and medium distances
Singlemode fibre (OS2)Campus and inter-building linksLong distance, future-proof capacity

In new projects, choosing Cat6A, especially for access points and PoE-powered devices, extends the life of the infrastructure. Cables stay in a building for decades; active equipment changes every few years.

Telecom rooms and routes

Floor telecom rooms are located together with the architectural and MEP designs so that horizontal cable lengths stay within the limit. These rooms receive power, UPS where needed, cooling and earthing. Low-current trays are separated from power cables to avoid electromagnetic interference, and tray routes are coordinated with other services in the BIM model.

Labelling, testing and documentation

Every cable, port and cabinet is named according to a labelling scheme such as TIA-606. After installation all copper and fibre links are tested with certification instruments and reported. As-built drawings and port lists are handed over, so faults and changes can be managed in minutes.

See our Services page for details of Sönmez Mühendislik's services, and our Blog for more technical articles.

Frequently asked questions

Click a question to see the answer.

Turkcell Data Center
BasicsWhich systems does structured cabling cover?
Computer networks, IP telephony, wireless access points, IP cameras, access control, building automation and other data-based systems.
ChoiceShould I choose Cat6 or Cat6A?
Cat6A is recommended for new projects. It supports 10 Gbit/s at 100 m and performs better with PoE-powered devices.
DistanceWhat is the cable length limit?
For copper horizontal cabling the permanent link is up to 90 m and the full channel 100 m. Fibre is used for longer distances.
Turkcell Data Center
RoomsIs a telecom room needed on every floor?
Several floors can be served from one room if horizontal length limits are met. Large floors may need more than one room.
TestingWhich tests are done after installation?
Category performance tests for copper and attenuation measurements for fibre, with a report for every link.
RoutesCan low-current and power cables share a tray?
It is not recommended. Separate trays or divided trays are used to prevent electromagnetic interference.

Let us design a future-ready data infrastructure for your building.

Since 1995, Sönmez Mühendislik has delivered structural, electrical, mechanical and BIM projects in Türkiye and abroad, and is one of Türkiye's long-established engineering offices. With more than 80 specialists we provide engineering design, technical consultancy and project management.